Cofem fire extinguishing control panel. 2 zones conventional system. Certified EN 54-2/4 and EN 12094-1

See delivery conditions


Are you an Installer or Specialized Store?
Become a PRO HERE! to see your special prices.

Right of withdrawal You have 14 calendar days to withdraw from your purchase, without providing any reason. More information
 

Specifications

  • Control panel with 2 zones with extinguishing functionality for use with conventional detectors and manual call points
  • Third additional zone configurable as a fire detection and alarm zone for conventional detectors and manual call points or as a monitoring input for an external fire protection system
  • 2 general siren outputs, 1 alarm output, 1 fault output, 2 30V DC outputs, test mode, threshold configuration, metal enclosure, etc
  • Normal Mode: R1 pre-extinguishing warning output is activated with Zone 1 or Zone 2 in alarm state
  • Consecutive Mode: R1 output is activated intermittently (1s with Zone 1 or Zone 2 in alarm state, 0.5s with Zones 1 and 2 in alarm state, and continuous once the delay of the R2 extinguishing output has ended)
  • Simultaneous Mode: R1 output is activated with Zones 1 and 2 in alarm state
  • 1 extinguishing stop button and 1 extinguishing activation button on the control panel
  • Possibility to install manual extinguishing stop and release call points in the flooding area
  • 1 extinguishing output (referred to as “R2”) supervised, delay adjustable between 0 and 60s, and protected by a resettable fuse
  • Delay of reset unlock after extinguishing activation programmable between 0 and 30 minutes
  • Modbus protocol with RS485 output on demand
  • Online PC software option using Modbus functionality
  • Contact ID on demand
  • Certified according to EN 54-2, EN 54-4 and EN 12094-1 standards with CE marking