NOTIFIER NOTIFIER-134 ITAC Notifier analog communication gateway for RP1r extinguishing panels

NOTIFIER-134
ITAC

DISCOUNTS AND LOWEST PRICE GUARANTEED: ASK US IN THE CHAT

IN STOCK - 24-48 business hours Spain and Portugal. Rest of Europe, bulky products and pallets: check lead times in the general terms and conditions.
-15% €366.57
€311.59
(tax incl.)
Time remaining

Por qué comprar NOTIFIER NOTIFIER-134 en Darkcoon

Best price guaranteed, official distributor of top brands, specialized technical support, fast shipping throughout Europe, official 3-year warranty, and Trusted Shops protection.

Interface module for integration into analog loops.

Free shipping* 24/48h

See delivery conditions

Are you an Installer or Specialized Store?
Become a PRO HERE! to see your special prices.

Right of withdrawal You have 14 calendar days to withdraw from your purchase, without providing any reason. More information
 

Technical features

  • Notifier analog-to-conventional communication gateway for extinguishing systems
  • Communication of events from RP1r Series extinguishing panels and HLSPS power supplies to analog panels
  • Integration with ID50/60, ID3000 and MAX panels via Clip protocol
  • Integration with AM-8200 panels via Advanced protocol
  • Supervised communications via the analog communications loop
  • Two rotary switches to select the start address on the loop

Functions

  • Transmission of pre-active status
  • Transmission of active status
  • Transmission of standby or stop mode
  • Transmission of key in manual mode
  • Transmission of key in disabled mode
  • Transmission of extinguishing completed
  • Transmission of general fault
  • Transmission of alarm or fault for zone 1, zone 2 and zone 3 in Advanced protocol
  • Addresses configurable in the analog panel as Monitor or Auxiliary modules
  • Not compatible with version 1.0

Alarms

  • Alarm for RP1r pre-active status
  • Active status of two alarms
  • RP1r in standby or stop mode
  • RP1r with key in manual mode
  • RP1r with key in disabled mode
  • Alarm for extinguishing completed
  • Extinguishing circuit fault
  • General panel fault

Communication interface

  • Connection from the gateway O/I to the panel or power supply AUX MOD via the included cable
  • Analog communications loop for supervised transmission
  • 7 monitor module addresses in Clip protocol
  • One address and 10 sub-addresses in Advanced protocol
  • Consecutive addresses in Clip protocol starting from the selected start address

Power supply

  • Powered from the extinguishing panel or the power supply via the included cable

Physical characteristics

  • Installation inside the integrated equipment or RP1r-SUPRA panel cabinet
  • Internal wiring to the panel or power supply AUX MOD connector

Contents

  • Notifier analog-to-conventional communication gateway NOTIFIER-134 (ITAC)
  • Connection wiring included