Interface module for integration into analog loops.
Free shipping* 24/48h
See delivery conditions
Right of withdrawal
You have 14 calendar days to withdraw from your purchase, without providing any reason. More information
Technical features
- Notifier analog-to-conventional communication gateway for extinguishing systems
- Communication of events from RP1r Series extinguishing panels and HLSPS power supplies to analog panels
- Integration with ID50/60, ID3000 and MAX panels via Clip protocol
- Integration with AM-8200 panels via Advanced protocol
- Supervised communications via the analog communications loop
- Two rotary switches to select the start address on the loop
Functions
- Transmission of pre-active status
- Transmission of active status
- Transmission of standby or stop mode
- Transmission of key in manual mode
- Transmission of key in disabled mode
- Transmission of extinguishing completed
- Transmission of general fault
- Transmission of alarm or fault for zone 1, zone 2 and zone 3 in Advanced protocol
- Addresses configurable in the analog panel as Monitor or Auxiliary modules
- Not compatible with version 1.0
Alarms
- Alarm for RP1r pre-active status
- Active status of two alarms
- RP1r in standby or stop mode
- RP1r with key in manual mode
- RP1r with key in disabled mode
- Alarm for extinguishing completed
- Extinguishing circuit fault
- General panel fault
Communication interface
- Connection from the gateway O/I to the panel or power supply AUX MOD via the included cable
- Analog communications loop for supervised transmission
- 7 monitor module addresses in Clip protocol
- One address and 10 sub-addresses in Advanced protocol
- Consecutive addresses in Clip protocol starting from the selected start address
Power supply
- Powered from the extinguishing panel or the power supply via the included cable
Physical characteristics
- Installation inside the integrated equipment or RP1r-SUPRA panel cabinet
- Internal wiring to the panel or power supply AUX MOD connector
Contents
- Notifier analog-to-conventional communication gateway NOTIFIER-134 (ITAC)
- Connection wiring included