¿Eres instalador o tienda especializada? !Hazte PRO y compra a precio mayorista!

  • Promoción
Buy TELETEK IVY-EX IVY conventional extinguishing panel with EN54 certificate
Buy TELETEK IVY-EX IVY conventional extinguishing panel with EN54 certificate

TELETEK IVY-EX IVY conventional extinguishing panel with EN54 certificate

IVY-EX

DISCOUNTS AND LOWEST PRICE GUARANTEED: ASK US IN THE CHAT

OUT OF STOCK - Stock on the way or available on backorder. Contact us for lead time or alternatives.
-8% €401.72
€369.58
(tax incl.)
Time remaining

Por qué comprar TELETEK IVY-EX en Darkcoon

Best price guaranteed, official distributor of top brands, specialized technical support, fast shipping throughout Europe, official 3-year warranty, and Trusted Shops protection.

IVY conventional extinguishing panel with EN54 certificate

See delivery conditions


Are you an Installer or Specialized Store?
Become a PRO HERE! to see your special prices.

Right of withdrawal You have 14 calendar days to withdraw from your purchase, without providing any reason. More information
 

IVY conventional extinguishing panel with EN54 certificate

- Conventional fire extinguishing control panel.
- The panel is designed for use together with gas, powder,
aerosol, water and other types of active extinguishing systems.
- 2 Conventional zones for extinguishing.
- 1 Conventional zone for fire alarm.
- Low pressure input - supervised balanced input.
- Manual release input - supervised balanced input.
- Mode selection input - supervised balanced input to switch
between Manual and Automatic operating mode.
- Hold input - supervised balanced input.
- Enable/disable - supervised balanced input.
- Flow control - supervised balanced input.
- SND 1 (Siren 1) - Supervised, 24Vdc, 300mA.
- SND 2 (Siren 2) - Monitored, 24Vdc, 300mA.
- Stage 1 relay "Fire alarm" (NC, COM, NO), 5-30Vdc / 1A.
- Stage 2 relay "Extinguishing Activated" (NC, COM, NO), 5-30Vdc / 1A.
- Fault relay (NC, COM, NO), 5-30Vdc / 1A.
- Extinguishing output (EN 12094-1), Monitored, 24Vdc / 1A 5min, 24Vdc / 3A
20ms.
- Main power supply: 110-230Vac.
- Backup power supply: 2 x 12V / 7Ah.
- Power output: 26Vdc / 1,5A.
- Battery internal resistance Ri < 0,3?.
- Consumption 0,3A at 230Vac; 0,7 at 110Vac.
- Operating temperature -5°C to 40°C.
- Relative humidity resistance: (93 ± 3)% at 40°C.
- Dimensions (H x W x D): 324 x 314 x 82 mm.
- Weight (without batteries): 3.2 Kg.